deyecodes
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| deyecodes [2026/05/14 23:01] – jwan | deyecodes [2026/07/22 17:32] (current) – [Grid and AC Data] jwan | ||
|---|---|---|---|
| Line 26: | Line 26: | ||
| ====== Battery Data ====== | ====== Battery Data ====== | ||
| < | < | ||
| + | 70 Battery Charge (Daily) kWh 0.1 | ||
| + | 71 Battery Discharge (Daily) kWh 0.1 | ||
| 182 Battery Temperature °C 0.1 (Offset 1000) | 182 Battery Temperature °C 0.1 (Offset 1000) | ||
| 183 Battery Voltage V 0.01 | 183 Battery Voltage V 0.01 | ||
| 184 Battery SOC % 1 | 184 Battery SOC % 1 | ||
| + | 189 | ||
| 190 Battery Power W 1 (Signed) | 190 Battery Power W 1 (Signed) | ||
| 191 Battery Current A 0.1 (Signed) | 191 Battery Current A 0.1 (Signed) | ||
| 105 Battery Daily Charge kWh 0.1 | 105 Battery Daily Charge kWh 0.1 | ||
| 106 Battery Daily Discharge kWh 0.1 | 106 Battery Daily Discharge kWh 0.1 | ||
| - | 102 Battery Total ChargekWh 0.1 | + | 102 Battery Total Charge kWh 0.1 |
| (Lifetime) | (Lifetime) | ||
| 103 Battery Total Discharge kWh 0.1 | 103 Battery Total Discharge kWh 0.1 | ||
| Line 44: | Line 47: | ||
| ====== Grid and AC Data ====== | ====== Grid and AC Data ====== | ||
| < | < | ||
| - | 160 Grid Voltage V 0.1 | + | 79 Grid Frequency |
| - | 161 Grid | + | 150 Grid Voltage |
| + | 151 Grid Voltage L2 | ||
| + | 157 Load Voltage | ||
| + | 160 Grid Current L1 A 0.1 | ||
| + | 161 Grid | ||
| 166 GRID Power (Total) W 1 (Signed) | 166 GRID Power (Total) W 1 (Signed) | ||
| 167 Grid L1 Power (Internal CT) W 1 (Signed) | 167 Grid L1 Power (Internal CT) W 1 (Signed) | ||
| - | 169 External CT / Check Meter Power W 1 (Signed) | + | 168 Grid L2 Power (Internal CT) |
| + | 169 External CT / Check Meter Power W 1 (Signed) | ||
| + | 170 Grid L1 Power (External CT) | ||
| + | 171 Grid L2 Power (External CT) | ||
| 175 Inverter Power (AC Output) W 1 (Signed) | 175 Inverter Power (AC Output) W 1 (Signed) | ||
| + | 176 Load L1 Power | ||
| + | 177 Load L2 Power | ||
| 178 Load Power (Essential) W 1 | 178 Load Power (Essential) W 1 | ||
| 84 Total Load Power kWh 0.1 | 84 Total Load Power kWh 0.1 | ||
| Line 69: | Line 81: | ||
| </ | </ | ||
| - | ====== | + | ====== |
| < | < | ||
| + | 0 Modbus Protocol Version Decimal | ||
| + | 1 Control Software Version (Firmware) Decimal | ||
| + | 2 Communication Board Version Decimal | ||
| + | 13 Rated Power (e.g., 6000 for 6kW) Watts | ||
| </ | </ | ||
| - | ====== Battery Data ====== | + | Note: |
| + | To compute for the temperature, | ||
| + | |||
| + | |||
| + | |||
| + | |||
| + | https:// | ||
| < | < | ||
| + | |||
| + | Production | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Total Production kWh 0x0060 | ||
| + | Daily Production kWh 0x006C | ||
| + | PV | ||
| + | |||
| + | Sensor Unit Register | ||
| + | PV1 Voltage V 0x006D | ||
| + | PV1 Current A 0x006E | ||
| + | PV1 Power W computed (V × I) | ||
| + | PV2 Voltage V 0x006F | ||
| + | PV2 Current A 0x0070 | ||
| + | PV2 Power W computed (V × I) | ||
| + | Total PV Power W computed (PV1 + PV2) | ||
| + | Max Solar Power W 0x0035 | ||
| + | Grid | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Grid Voltage 1 V 0x0096 | ||
| + | Grid Voltage 2 V 0x0097 | ||
| + | Grid Power W 0x00A9 | ||
| + | Load | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Daily Load Consumption kWh 0x0054 | ||
| + | Total Load Consumption kWh 0x0055 | ||
| + | Load L1 Voltage V 0x009D | ||
| + | Load L1 Current A 0x00A4 | ||
| + | Load L1 Power W 0x00B2 | ||
| + | Total Load Power W 0x00B0 | ||
| + | Inverter | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Total Power W 0x00AD | ||
| + | Inverter L1 Power W 0x00AF | ||
| + | DC Temperature °C 0x005A | ||
| + | AC Temperature °C 0x005B | ||
| + | Battery | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Battery Voltage V 0x00B7 | ||
| + | Battery Current A 0x00BF | ||
| + | Battery Power W 0x00BE | ||
| + | Battery SOC % 0x00B8 | ||
| + | Battery Settings (diagnostic) | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Battery Capacity Ah 0x00CC | ||
| + | Battery Empty Voltage V 0x00CD | ||
| + | Max Charge Current A 0x00D2 | ||
| + | Max Discharge Current A 0x00D3 | ||
| + | Battery Shutdown % % 0x00D9 | ||
| + | Battery Restart % % 0x00DA | ||
| + | Battery Low % % 0x00DB | ||
| + | Selling Mode (diagnostic) | ||
| + | |||
| + | Sensor Unit Register | ||
| + | Selling Mode Time 1–6 HH: | ||
| + | Selling Mode Power 1–6 W 0x0100–0x0105 | ||
| + | Selling Mode SOC 1–6 % 0x010C–0x0111 | ||
| + | Selling Mode Charge Flag 1–6 — 0x0112–0x0117 | ||
| </ | </ | ||
| + | |||
| + | [[deyecodedefinition|Deye Code Definition (from Solarman)]] | ||
| + | |||
deyecodes.1778799713.txt.gz · Last modified: by jwan